消防设施通用规范(GB 55036-2023)第10.0.1条
10.0.1 灭火器的配置类型应与配置场所的火灾种类和危险等级相适应,并应符合下列规定:
1 A类火灾场所应选择同时适用于A类、E类火灾的灭火器。
2 B类火灾场所应选择适用于B类火灾的灭火器。B类火灾场所存在水溶性可燃液体(极性溶剂)且选择水基型灭火器时,应选用抗溶性的灭火器。
3 C类火灾场所应选择适用于C类火灾的灭火器。
4 D类火灾场所应根据金属的种类、物态及其特性选择适用于特定金属的专用灭火器。
5 E类火灾场所应选择适用于E类火灾的灭火器。带电设备电压超过1kV且灭火时不能断电的场所不应使用灭火器带电扑救。
6 F类火灾场所应选择适用于E类、F类火灾的灭火器。
7 当配置场所存在多种火灾时,应选用能同时适用扑救该场所所有种类火灾的灭火器。
General Specifications for Fire ProtectionFacilities (GB 55036-2023), Article 10.0.1
The configuration type of fire extinguisher shall be compatible with the fire type and hazard level of the location, and shall comply with the following provisions:
1. Fire extinguishers suitable for Class A and E fires shall be selected for Class A fire places.
2. Fire extinguishers suitable for Class B fire shall be selected for Class B fire places. When there is water-soluble flammable liquid (polar solvent) in Class B fire places and water-based fire extinguisher is selected, the fire extinguisher with solubility resistance shall be selected.
3. Fire extinguishers suitable for Class C fire shall be selected for Class C fire places.
4. For Class D fire places, special fire extinguishers suitable for specific metal shall be selected according to the type, physical state and characteristics of metal.
5. Fire extinguishers suitable for Class E fire shall be selected for Class E fire places. Fire extinguishers shall not be used for live fire fighting in places where the voltage of live equipment exceeds 1kV and the power cannot be cut off during fire fighting.
6. Fire extinguishers suitable for Class E and F fires shall be selected for Class F fire places.
7. When there are multiple fires in the configuration site, the fire extinguisher that can simultaneously put out all kinds of fires in the site shall be selected.
更新日期:2023-02-20